Oil-Mist 150

OMR 150

HIGH TEMP OIL-MIST RESISTANT WIRE

Ratings/Approvals:

  • 150°C – 1000 Volts – UL Style 3644 / CSA AWM I A/B FT2

Construction:

  • Conductors
    • 24 AWG – 750 MCM
    • Stranded tinned copper
  • Insulating System
    • Oil Mist Rubber
  • Standard Color Coding
    • Gray or white only.

Characteristics:

  • Specially formulated to resist swelling and tearing in oil mist applications and provided added abrasion resistance
  • Outperforms Braided Silicone products
    • Eliminates braid fraying, flowering, and shrink back
    • Virtually eliminates skin irritation
    • Reduces airborne fiberglass contaminants traditionally found in high volume processing
    • Superior flexibility
    • Color stable at elevated temperatures
    • Low smoke, zero halogen
    • Suitable for varnish dip and bake applications
    • Smaller OD
  • Silicone formulations suitable for UV, ozone, moisture exposure. Not suited for immersed applications
  • Suitable for applications to -60°C

SPECIFICATIONS

Oil-Mist 150

HIGH TEMP OIL-MIST RESISTANT WIRE

Download OMR 150 Specs

OMR 150C/1000V

Part No.Awg. Size# StrandsOuter Dia.
(in)
Outer Dia.
(mm)
Wgt
(lbs/Mft)
Min. Bend Radius
(in)
ULCSA 180C
NJO24T0072470.0852.164.270.683644AWM I A/B FT2
NJO22T0072270.0912.315.340.733644AWM I A/B FT2
NJO20T0072070.0982.496.930.783644AWM I A/B FT2
NJO18T0071870.1082.749.300.863644AWM I A/B FT2
NJO16T0071670.1203.0512.940.963644AWM I A/B FT2
NJO14T0071470.1333.3817.621.063644AWM I A/B FT2
NJO12T01912190.1503.8126.841.203644AWM I A/B FT2
NJO10T01910190.1734.3940.031.383644AWM I A/B FT2
NJO08T0618610.2345.9468.711.873644AWM I A/B FT2
NJO06T0846840.3378.56114.002.703644AWM I A/B FT2
NJO04T13341330.3719.42155.482.973644AWM I A/B FT2
NJO02T25922590.44611.33234.593.573644AWM I A/B FT2
NJO01T25912590.50712.88302.544.063644AWM I A/B FT2
NJOX1T2591/02590.56214.27383.574.503644AWM I A/B FT2
NJOX2T2592/02590.60815.44471.834.863644AWM I A/B FT2
NJOX3T2593/02590.65716.69581.875.263644AWM I A/B FT2
NJOX4T2594/02590.71718.21720.495.743644AWM I A/B FT2
NJO25T427250 MCM4270.81620.73869.696.533644AWM I A/B FT2
NJO35T427350 MCM4270.92623.521185.147.413644AWM I A/B FT2
NJO50T427500 MCM4271.05626.821621.958.453644AWM I A/B FT2
NJO75T703750 MCM7031.31833.482561.3510.543644AWM I A/B FT2

Standard conductor: Tinned Copper.