DuraLife® II Dual Rated CIC/CI

DuraLife® Multi-conductor Dual-Rated CIC/CI Cables

Shielded/Unshielded Fire Resistive Cables

Certified to the harsh requirements of the UL 2196 Test for Fire Resistive Cables, the DuraLife Multi-Conductor Dual-Rated CIC/CI Cables ensure two-hour operation of critical systems in the event of a fire. The dual rating design offers the most versatility in meeting code survivability requirements in both in-conduit and free air installation scenarios.

Description: Multi-Conductor Dual-Rated CIC/CI Cables. UL 2196 Certified/UL 1424 Listed.
FHIT System No. 28D. Low smoke, zero halogen design (LSZH).
FHIT7 System No. 28D
Sizes Available: 18-12 AWG unshielded; 18-14 AWG shielded. 4/C, 6/C, and 8/C Constructions

Construction:

  • Conductor: Oxygen-free bare copper (OFHC), solid and/or stranded
  • Insulation: Proprietary ceramifiable silicone rubber
  • Assembly: Numerically printed black/red paired leads
  • Jacket: Red low smoke/zero halogen FRPE with sequential footage markers (custom colors available/special order mins apply)

Applications:

  • Hospitals & Healthcare Facilities
  • High Rise & Mix Use Buildings
  • Universities & College Campuses
  • Stadiums, Casinos, Places of Assembly
  • Government Facilities

Critical Systems:

  • Fire Alarm and EVAC Systems
  • Smoke Evacuation and Control
  • Fan & Pressurization Systems
  • Strobes & Notification Appliances
  • Area of Refuge Systems
  • Emergency Lighting

COMPLIANCE:

  • UL 1424 Listed FPLR/FPLR-CI (dual-rated) for Power-Limited Fire Alarm Circuits. Riser Rated. 300V/105°C classified.
  • UL / CAN (ULC formerly S-139) Certified to UL 2196 2-hour fire rating in FHIT / FHIT7 28C
  • CSA Certified to CSA Std. C22.2 No. 208; Type FAS90, 300V/90C FT4-ST1
  • UL Certified 2-hour fire rating as FPLR-CI for Free Air installed per NEC code
  • Fire alarm circuit integrity, emergency systems, and healthcare facilities (NEC Articles 760, 700 & 517)
  • Meets National Fire Protection Code (NFPA 130 & 502) fire alarm survivability circuit requirements
  • Compliance tested to UL 1424 as suitable for use in applications requiring wet rating
  • Meets UL1685 and FT4/IEEE 1202 requirements
  • Tested for Sunlight Resistance in compliance with UL 2556 requirements
  • Suitable for 2-hour certified fire-resistive applications in EMT or IMC conduit systems
  • UL Listed File No. E-241484. UL Fire Directory R-21213
  • CAFM approved

HARDWARE CERTIFIED: (Refer to DuraLife® II Multi-Conductor Installation Guide for additional details)

  • EMT/IMC Conduit: Wheatland/Western Tube
  • EMT/IMC Conduit: Allied/Columbia (EMT: E-Z Pull Brand)
  • NEMA 1 Splice Enclosure/Pull Box: Eaton/Cooper
  • Pulling Lubricant: Polywater LZ
  • Connectors and Couplings:
    • Compression – Cooper Crouse-Hinds (EMT); Hubbell-Raco (EMT/IMC)
    • Set Screw – Hubbell-Raco (EMT/IMC)
  • Splice Connector: 3M Butt-Type Crimp Terminals
  • Splice Tapes – 1″: 3M Silicone; St. Gobain Fiberglass Tape

SPECIFICATIONS

DuraLife® Multi-conductor Dual-Rated CIC/CI Cables

Shielded/Unshielded Fire Resistive Cables

Download DuraLife® Multi-Conductor Dual-Rated CIC/CI Cables Spec

UNSHIELDED

RADIX P/NAWG/ COND.*SOLID OR STRANDEDNOMINAL O.D. (INCH)COND. RESISTANCE (OHMs/FT)NOM.CAP. (pF/FT) (per pair)EMT/IMC UNSHIELDED MAX CABLE FILL ALLOWANCE (for in-conduit installations per FHIT 28D)
¾”1″1 ¼”1 ½”2″
CTU18A010318/3CSolid.330″6.48124610
CTU18A010418/4CSolid.366″6.4814.4124610
CTU18A010518/5CSolid.410″6.4811347
CTU18A010618/6CSolid.444″6.4814.411347
CTU18A010718/7CSolid.490″6.48X1235
CTU18A010818/8CSolid.518″6.4814.4X1235
CTU16A010316/3CSolid †.380″3.9912348
CTU16A010416/4CSolid †.405″3.9915.312348
CTU16A010516/5CSolid †.450″3.99X1235
CTU16A010616/6CSolid †.485″3.9915.3X1235
CTU16A010716/7CSolid †.530″3.99X1124
CTU16A010816/8CSolid †.575″3.9915.3X1124
CTU14A010314/3CSolid †.405″2.5711347
CTU14A010414/4CSolid †.431″2.5717.111347
CTU14A010514/5CSolid †.485″2.57X1235
CTU14A010614/6CSolid †.523″2.5717.1X1235
CTU14A010714/7CSolid †.570″2.57XX123
CTU14A010814/8CSolid †.629″2.5717.1XX123
CTU12A070312/3C7-Strand**.460″1.64X1235
CTU12A070412/4C7-Strand**.483″1.6417.6X1235
CTU12A070512/5C7-Strand**.590″1.64XX123
CTU12A070612/6C7-Strand**.633″1.6417.6XX123
CTU12A070712/7C7-Strand**.670″1.64XX112
CTU12A070812/8C7-Strand**.708″1.6417.6XX112

* Numerically printed black/red paired leads; with black lead on odd numbered constructions
† 16AWG and 14 AWG constructions also available stranded
** 12 AWG construction also available in solid

SHIELDED

RADIX P/N#CONDSOLID OR STRANDEDNOMINAL O.D. (INCH)COND. RESISTANCE (OHMs/FT)NOM. CAP. (pF/FT) (per pair)EMT/IMC SHIELDED MAX CABLE FILL ALLOWANCE (for in-conduit installations per FHIT 28D)
¾”1″1 ¼”1 ½”2″
CTS18A010318/3CSolid.355″6.4812455
CTS18A010418/4CSolid.389″6.4818.412455
CTS18A010518/5CSolid.445″6.4811233
CTS18A010618/6CSolid.472″6.4818.411233
CTS18A010718/7CSolid.525″6.48X1122
CTS18A010818/8CSolid.551″6.4818.4X1122
CTS16A010316/3CSolid †.400″3.9912358
CTS16A010416/4CSolid †.411″3.9919.112358
CTS16A010516/5CSolid †.470″3.99X1235
CTS16A010616/6CSolid †.492″3.9919.1X1235
CTS16A010716/7CSolid †.560″3.99X1124
CTS16A010816/8CSolid †.583″3.9919.1X1124
CTS14A010314/3CSolid †.430″2.5711246
CTS14A010414/4CSolid †.463″2.5721.411246
CTS14A010514/5CSolid †.505″2.57X1124
CTS14A010614/6CSolid †.562″2.5721.4X1124
CTS14A010714/7CSolid †.600″2.57XX113
CTS14A010814/8CSolid †.676″2.5721.4XX113

*Numerically printed black/red paired leads; with black lead on odd numbered constructions
† 16 AWG and 14 AWG constructions also available stranded