AMPACITY RATINGS
CURRENT CARRYING CAPACITY TABLE
BASE TEMPERATURE AT 40 C
|
150 C
Tinned Copper |
200 C
Tinned Copper
NPC 2%-10% |
250 C
NPC 2%-10% |
250 C
"A" Nickel
|
250 C
NPI |
450 C
NPC-27% |
450 C
"A" Nickel |
| 24 |
6.6 |
7.2 |
8 |
4 |
3.3 |
9 |
4.3 |
| 22 |
9 |
9.6 |
10.8 |
5 |
4.4 |
12 |
5.6 |
| 20 |
13 |
14 |
15 |
7 |
6 |
18 |
8 |
| 18 |
17 |
18 |
20 |
9.4 |
8 |
23 |
11 |
| 16 |
22 |
24 |
26 |
12 |
11 |
30 |
14 |
|
|
14 |
34 |
36 |
39 |
18 |
16 |
45 |
21 |
|
12 |
43 |
45 |
54 |
25 |
22 |
56 |
26 |
|
10 |
55 |
60 |
73 |
34 |
30 |
75 |
35 |
|
8 |
76 |
83 |
93 |
43 |
39 |
104 |
49 |
|
|
6 |
96 |
110 |
117 |
55 |
49 |
138 |
65 |
|
4 |
120 |
125 |
148 |
69 |
62 |
162 |
76 |
|
3 |
143 |
152 |
166 |
78 |
69 |
182 |
85 |
|
2 |
160 |
171 |
191 |
90 |
80 |
210 |
99 |
|
1 |
186 |
197 |
215 |
101 |
90 |
236 |
110 |
|
|
1/0 |
215 |
229 |
244 |
114 |
102 |
268 |
126 |
|
2/0 |
251 |
260 |
273 |
128 |
114 |
300 |
141 |
|
3/0 |
288 |
297 |
308 |
144 |
129 |
338 |
159 |
|
4/0 |
332 |
346 |
361 |
169 |
151 |
397 |
186 |
|
|
250 |
365 |
385 |
398 |
187 |
167 |
-- |
-- |
|
300 |
414 |
436 |
452 |
212 |
190 |
-- |
-- |
|
350 |
461 |
486 |
503 |
236 |
211 |
-- |
-- |
|
400 |
495 |
522 |
540 |
254 |
226 |
-- |
-- |
|
500 |
563 |
593 |
613 |
288 |
257 |
-- |
-- |
NOTE: For allowable ampacities for fixture wires used in fixtures, see Article 402 and Table 402.5 in 1996 National Electrical Code Handbook.